Prestressed I-girders
A prestressed girder is rated twice for the same truck: for strength, where the strands act like reinforcing bars, and for cracking, where the prestress left in the strands is the capacity. The cracking check is often the lower one.
Permit check: strength and the bottom strand
A heavy permit is checked at Strength II and, for prestressed concrete, at Service I: the bottom strand must stay below 0.9 fpy so the girder closes up again after the load has passed.
Key points
- Two checks for one truck. Strength I treats the strands as reinforcement. Service III checks the bottom fibre on the uncracked section: the compression from the prestress plus the allowed tension is the capacity.
- Losses only hurt cracking. Every ksi of loss comes out of the bottom-fibre compression. The strength rating barely changes, because the strand stress at failure does not depend on the prestress left.
- The tension limit matters. Moderate exposure allows 0.19√f′c; deicing salt counts as severe and allows half that. That choice alone can move Service III across 1.0.
- No φ at service. Condition and system factors cut strength only. A girder in poor condition can switch from cracking-governed to strength-governed.
- Permits check the strand. Strength II uses the one-lane factor without the 1.2; Service I keeps the ordinary multi-lane factor. Once the permit cracks the girder, the strand stress rises fast.
Rate prestressed members on the gross section, with losses from the AASHTO approximate method (defaults: 75-year life, transfer at 24 hours, deck at 28 days, 80% humidity); use the refined method if the ratings come out low or the member is non-composite. PCI and lump-sum losses are not allowed. Poor condition uses φc = 0.90. VDOT does not allow elastic gains in losses, so the Service III factor stays at 0.8 unless the Load Rating Program Manager agrees otherwise; VDOT's BrR settings leave the legal Service III and permit Service I checks off unless the district asks for them. VDOT IIM-S&B-86.5 §11.1, §11.3 (p.5) · IIM-S&B-80.10 p.8 · VDOT-LR-G6 pp.23, 27
Quick check
On Example 1, the losses turn out to be 15 ksi higher than computed. What happens?
Losses reduce the compression in the bottom fibre, which is most of the Service III capacity. The strength rating does not use the prestress that is left. Set ΔfpT to 50.3 in Example 1 and Service III falls below 1.0.
The Type II girder of Example 3 is repaired and its condition goes back to Fair (φc = 1.00). Which rating changes?
The condition factor multiplies the strength. There is no resistance, condition or system factor at the service limit state, so Service III stays where it was.
A permit truck is made 20% heavier. On a girder that it already cracks, the strand stress rises…
Above the cracking moment the extra moment acts on the cracked section, which is much softer, so most of it goes into the strand. Below cracking the strand stress hardly moves. See the first what-if on the permit sheet.
Sources
- FHWA-NHI 130092, LRFR participant workbook, Lesson 15 (pp. 509–538), with the section data of Lesson 13 (PW 13.19–13.32).
- AASHTO MBE 3rd Ed., 6A.4.2, Tables 6A.4.2.2-1 and 6A.4.2.2-2 (errata p.8), 6A.4.5.4.2a, 6A.5.4.2.2b.
- AASHTO LRFD BDS 8th Ed., 4.6.2.2, 5.6.3.1.1, 5.6.3.2.2, 5.6.3.3, 5.9.2.3.2b and C5.9.2.3.2b (PDF pp. 475–476), 5.9.3.3.
- VDOT IIM-S&B-86.5 §11.1 and §11.3 (p.5); IIM-S&B-80.10 p.8; VDOT load rating guideline LR-G6 pp.23, 27.
- Own examples use standard AASHTO Type II, III and IV properties with composite sections, distribution factors and approximate losses worked out for these spans; shear resistances are estimates.
A study aid, not a substitute for the AASHTO MBE or an agency's rating procedures. Example numbers are illustrative.