Condition and section loss
A deteriorated member loses strength twice: once for the steel or concrete that is gone, and once more through the condition factor. The bridge's own weight does not shrink, so the whole loss comes out of the part left for traffic.
Key points
- Two separate cuts. The nominal resistance Rn uses the section as inspected: measured thicknesses, remaining bar area. The condition factor φc then covers the larger scatter of a decaying member and further loss before the next inspection.
- φc does not replace measurements. Section loss must be in Rn. Ask for remaining thicknesses, with size and location of the loss, before rating.
- Loss is leveraged. If dead load uses 40% of the strength, a 10% loss of strength costs 17% of the rating. Long, heavy spans feel deterioration the most.
- Condition factor by the MBE: 1.00 for good or satisfactory (NBI 6 or more), 0.95 for fair (5), 0.85 for poor (4 or less). Add 0.05 if the losses were measured, up to 1.00. It applies to the deteriorated members, at strength only.
- The 0.85 floor. φc × φs is never taken below 0.85, so a poor, non-redundant member is not penalised twice without limit.
- No plans for a concrete bridge? If it has carried normal traffic for a long time with no distress, it need not be posted; inspect it regularly and document the decision. A load test is the other route.
Unless the District Bridge Engineer says otherwise, φc is 1.0 for good, satisfactory or fair and 0.9 for poor. The IIM does not mention the MBE's +0.05 for measured loss, so this sheet does not apply it under the VDOT rules. A bridge is re-rated when its General Condition Rating falls to 4 or below. Load testing is allowed when analysis seems conservative, and VDOT excludes the MBE 6B.7.1 paragraph that rates culverts under fill from their service record. VDOT IIM-S&B-86.5 §4, §4.2, §10, §11.1
Quick check
Dead load uses half of a girder's usable strength. Corrosion takes 10% off the strength. Roughly how much does the rating factor drop?
Only half the strength was left for traffic, and the whole 10% comes out of that half: 10% / (1 − 0.5) = 20%.
Open Example 1 and switch the condition factor rules to the MBE. What happens?
The loss was measured with calipers, so the MBE lets 0.85 go up by 0.05, which matches VDOT's 0.90. Untick "section loss measured" to see the MBE's plain 0.85.
An inspection report says "heavy rust and pitting on the bottom flange", with no thicknesses. What should the rater do?
The condition factor is added on top of the as-inspected section; it is not a stand-in for the loss itself. Visual estimates can be wrong in either direction.
Sources
- FHWA-NHI 130092, LRFR participant workbook, Lesson 9 (pp. 299–324). Lesson 9 has no numerical exercise; the workbook check uses the Lesson 8 group exercise girder (PW 8.24, solution p. 827).
- AASHTO MBE 3rd Ed., 6A.4.2.3 with Table 6A.4.2.3-1 and Table C6A.4.2.3-1 (condition factor), Table 6A.4.2.4-1 (system factor), Eq. 6A.4.2.1-3 (0.85 floor), 6B.7.1 (unknown reinforcement), Section 8 (load testing); as reprinted in the errata, AASHTO-MBE-3-ERRATA pp. 8–10, 27.
- VDOT IIM-S&B-86.5, §4 and §4.2 (evaluation, re-rating), §9 (engineering judgment), §10 (load testing), §11.1 and Table 2 (condition factor).
A study aid, not a substitute for the AASHTO MBE or an agency's rating procedures. Example numbers are illustrative.