Strength, service and fatigue
Strength asks "will the member fail?". Service asks "will it be damaged?": a flange that yields and stays bent, a beam that cracks. This sheet rates one member both ways, and checks a steel detail for fatigue.
Key points
- Strength is always rated. The service check depends on the material: Service II for steel, Service III (cracking) for prestressed concrete, Service I for concrete under permit loads. Timber has none.
- Same equation, in stresses. The capacity is a stress limit, such as 0.95Fy for a composite steel flange. There are no φ, φc or φs factors, and dead load is taken at 1.00.
- Each load acts on its own section. Dead load poured before the deck hardens sits on the bare girder. Barriers and overlay sit on the long-term composite section, and trucks on the short-term one. That is why service can govern even when strength has room.
- "Optional" does not mean "skip". An optional check need not drive a posting or permit decision. It still tells you how the bridge behaves under today's trucks.
- Fatigue never posts a bridge. RF = threshold / (1.75 × stress range). Below 1, the detail does not have infinite life: do a finite-life check and plan hands-on inspection (Lesson 22).
Fatigue evaluation of steel bridges is optional; the District Structure and Bridge Engineer decides whether it is considered. VDOT's BrR guidance treats concrete service ratings as optional, except for segmental bridges, and asks that BrR's Service II ratings for emergency vehicles be corrected to a live load factor of 1.3. VDOT IIM-S&B-86.5 §11.4; VDOT LR G6 pp.2, 16
Quick check
At inventory, a composite steel beam gives Strength I RF = 1.30 and Service II RF = 1.10. What is its inventory rating?
Both checks are required at inventory, and the lower one governs: 1.10, set by flange yielding.
On Example 1, change the condition factor φc to Poor (0.90). Which rating factor moves?
The condition and system factors belong to the strength limit state only. Service II compares stresses with 0.95Fy and does not see them.
A cover plate end gives fatigue RF = 0.6, while strength and service pass. What follows?
Fatigue is not a posting check. An RF below 1 means the detail may crack in time, so the owner estimates its remaining life and inspects or retrofits it.
Sources
- FHWA-NHI 130092, LRFR participant workbook, Lesson 7 (pp. 247–266); the workbook check uses the Lesson 21 guided example, MBE Example A1 (pp. 684–695, solutions pp. 844–848).
- AASHTO MBE 3rd Ed., Table 6A.4.2.2-1 (limit states and load factors), Eq. 6A.4.2.1-1, C6A.5.4.2.2b (Service I), 6A.6.4 (steel service and fatigue).
- AASHTO LRFD BDS, Table 6.6.1.2.5-3 (fatigue thresholds).
- VDOT IIM-S&B-86.5, §11.4 (fatigue); VDOT load rating guideline G6 (BrR), pp. 2, 16.
A study aid, not a substitute for the AASHTO MBE or an agency's rating procedures. Example numbers are illustrative.